Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2018, 08:26 AM
  • 08 0205_08 0204 _21122018_002653.mp4

Date
12/21/2018
W/O
740635
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00010
PipeID
P00265
Time
12:26 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6254
Sewer Name
08 GRACE STREET TRUNK, SECTS 2&3
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_740635_TV08022_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0204
Downstream MH
08 0205
Dir. of Survey
Upstream
Length Surveyed
323.6 ft.
Total Length
323.6 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
192
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
192
Pipe schematic from manhole 08 0204 to 08 0205
MH: 08 0204MH: 08 0205upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 02050 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish74.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"105.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"151 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"272.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"299.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"320.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start323.6 ft. MWM - Water Mark, 15 %of cross sectional area323.6 ft. AMH - Downstream Manhole, Survey Begins - 08 0204323.6 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
323.6AMH08 0205
0MWM
0AMH08 0204
218TFC
195.4TFC
51.3TFC
248.8TFC
3.1CM
172.6TFC
0MWL
323.6CM
24.5TFC
123.4TFC
100.5TFC
150TF
73.8TFC

Properties (6)

additional_info
SC365487
custom_field_two
3
customer
LACSD
datetime
2018-12-21T00:26:37-08:00
documentation
PROPIPE
is_lateral_inspection
false