Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2018, 06:05 AM
  • 08 0207_08 0206 _20122018_220542.mp4

Date
12/20/2018
W/O
740635
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00010
PipeID
P00267
Time
10:05 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6254
Sewer Name
08 GRACE STREET TRUNK, SECTS 2&3
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_740635_TV08022_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0207
Downstream MH
08 0206
Dir. of Survey
Downstream
Length Surveyed
349.7 ft.
Total Length
349.7 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
209
Pipe schematic from manhole 08 0207 to 08 0206
MH: 08 0207MH: 08 0206downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02075.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"12.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES29.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"102 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES107.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"151.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"293 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"334.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"337.4 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"345.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK349.7 ft. AMH - Downstream Manhole, Survey Ends - 08 0206

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    12.9 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

    337.4 ft. - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

Observations (25)

DistanceCodeObservation
349.7MGOCONNECTION AT MH 3 O'CLOCK
303.2TF
151.5TF
5.7CM
0MWM
334.2TFC
12.9FL
0MWL
106.4DAGS
254.2TFC
102TFC
29.8TFC
198.5TFC
0AMH08 0207
345.1CM
349.7AMH08 0206
68.6TF
205.1TFC
91.3TFC
293TF
124.7TFC
107.2TFA
227.4TFC
337.4TB
11.3TFC

Properties (6)

additional_info
SC365487
custom_field_two
3
customer
LACSD
datetime
2018-12-20T22:05:33-08:00
documentation
PROPIPE
is_lateral_inspection
false