Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2018, 06:28 AM
  • 08 0205A_08 0205 _20122018_222909.mp4

Date
12/20/2018
W/O
740635
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00010
PipeID
P00266
Time
10:28 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6254
Sewer Name
08 GRACE STREET TRUNK, SECTS 2&3
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_740635_TV08022_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0205A
Downstream MH
08 0205
Dir. of Survey
Downstream
Length Surveyed
132.6 ft.
Total Length
132.6 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
78
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
78
Pipe schematic from manhole 08 0205A to 08 0205
MH: 08 0205AMH: 08 0205downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 0205A4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish132.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0205

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    28.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
0MWM
132.6CM
132.6AMH08 0205
28.9TB
40.2TFC
5.4TF
90.5TFC
0MGOCONNECTION AT MH 3 O'CLOCK
4CM
0MWL
0AMH08 0205A

Properties (6)

additional_info
SC365487
custom_field_two
3
customer
LACSD
datetime
2018-12-20T22:28:38-08:00
documentation
PROPIPE
is_lateral_inspection
false