Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2018, 05:30 AM
  • 08 0209_08 0208 _20122018_214619.mp4

Date
12/20/2018
W/O
740635
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00010
PipeID
P00269
Time
9:30 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6254
Sewer Name
08 GRACE STREET TRUNK, SECTS 2&3
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_740635_TV08022_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0209
Downstream MH
08 0208
Dir. of Survey
Downstream
Length Surveyed
245.1 ft.
Total Length
245.1 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 08 0209 to 08 0208
MH: 08 0209MH: 08 0208downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 02090 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area3.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES10.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"16.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"56.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK245.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish245.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0208

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    130.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (21)

DistanceCodeObservation
56.9TFC
130.6TB
0MGOCONNECTION AT MH 3 O'CLOCK
0AMH08 0209
232.5TF
10.7TFC
160.3TFC
0MWL
63.5TFC
9CM
16.3CM
0MWM
245.1MGOCONNECTION AT MH 9 O'CLOCK
245.1CM
245.1AMH08 0208
209.9TFC
133.5TFC
182.7TFC
98.6TFC
34.1TFC
3.6CM

Properties (6)

additional_info
SC365487
custom_field_two
3
customer
LACSD
datetime
2018-12-20T21:30:02-08:00
documentation
PROPIPE
is_lateral_inspection
false