Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2019, 06:29 PM
  • 30 0226_30 0223_5302019_113144.mp4

Date
05/30/2019
W/O
0771073
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00884
PipeID
P17926
Time
11:29 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7990
Sewer Name
30 VIA CAMPESINA TRUNK
City
PALOS VERDES ESTATES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20190529DF_VIA_CAMPESINA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
30 0226
Downstream MH
30 0223
Dir. of Survey
Downstream
Length Surveyed
111.1 ft.
Total Length
111.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 30 0226 to 30 0223
MH: 30 0226MH: 30 0223downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:30 AM0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start27.4 ft. MGP - General Photograph47.3 ft. MGP - General Photograph83.2 ft. MGP - General Photograph102.1 ft. MGP - General Photograph102.9 ft. MGP - General Photograph104.5 ft. RFJ - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YESR, Start111.1 ft. MSA - Survey Abandoned - DEBRIS111.1 ft. RFJ - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YESR, Finish111.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish111.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish111.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish

Observation photos (8)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    4 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • General Photograph

    27.4 ft. - General Photograph

  • General Photograph

    47.3 ft. - General Photograph

  • General Photograph

    83.2 ft. - General Photograph

  • General Photograph

    102.1 ft. - General Photograph

  • General Photograph

    102.9 ft. - General Photograph

Observations (17)

DistanceCodeObservation
102.9MGP
102.1MGP
111.1MSADEBRIS
111.1RFJ
111.1SSS
2SSS
83.2MGP
104.5RFJ
0MWM
0AMH11:30 AM
27.4MGP
111.1CM
111.1RFJ
2CM
47.3MGP
0MWL
4RFJ

Properties (5)

custom_field_two
5
customer
LACSD
datetime
2019-05-30T11:29:29-07:00
documentation
FRANKLIN, BRAR, CASTILLO
is_lateral_inspection
false