Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2019, 08:52 AM
  • B 0584_B 0583 _04022019_020326.mp4

Date
04/02/2019
W/O
756625
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00104
PipeID
P09155
Time
1:52 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6508
Sewer Name
B JOINT OUTFALL B - UNIT 8A
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
22
Purpose
Routine Assessment
Project
WO_756625_TV15054_MAR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
B 0584
Downstream MH
B 0583
Dir. of Survey
Downstream
Length Surveyed
74.9 ft.
Total Length
74.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole B 0584 to B 0583
MH: B 0584MH: B 0583downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 05840 ft. MWM - Water Mark, 40 %of cross sectional area6.2 ft. MGO - General Observation - MAG COAT6.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start71.5 ft. MGO - General Observation - MAG COAT71.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish74.9 ft. AMH - Downstream Manhole, Survey Ends - B 058374.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
74.9AMHB 0583
0MGOCONNECTION AT MH 3 O'CLOCK
71.5MGOMAG COAT
6.2MGOMAG COAT
74.9MGOCONNECTION AT MH 9 O'CLOCK
6.2SAV
0MWL
0AMHB 0584
0MWM
71.5SAV

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-04-02T01:52:09-07:00
documentation
PROPIPE
is_lateral_inspection
false