Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2018, 08:36 AM
  • 32 0158_32 0157 _07252018_020926.mp4

Date
07/25/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19910
Time
1:36 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5880
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0157
Downstream MH
32 0158
Dir. of Survey
Upstream
Length Surveyed
424.3 ft.
Total Length
424.3 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
252
O&M Index
2
O&M Quick
2P00
O&M Rating
168
Overall Index
3
Overall Quick
Overall Rating
420
Pipe schematic from manhole 32 0157 to 32 0158
MH: 32 0157MH: 32 0158upstream0 ft. AMH - Upstream Manhole, Survey Ends - 32 01580 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish422.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start422.3 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start424.3 ft. AMH - Downstream Manhole, Survey Begins - 32 0157424.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE424.3 ft. MWM - Water Mark, 15 %of cross sectional area424.3 ft. MGO - General Observation - MAG COATING THROUGHOUT 70%424.3 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    424.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
424.3AMH32 0158
0AMH32 0157
0MGOCOCKROACHES IN MANHOLE
2DAGS
2SAP
424.3MGOCOCKROACHES IN MANHOLE
422.3DAGS
0MWM
0MGOMAG COATING THROUGHOUT 70%
422.3SAP
0MWL

Properties (6)

additional_info
SC359748
custom_field_two
2
customer
LACSD
datetime
2018-07-25T01:36:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false