Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 18, 2018, 10:11 AM
  • 32 0115_32 0114_08202018_031335.mp4

Date
07/18/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19860
Time
3:11 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6006
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
32 0115
Downstream MH
32 0114
Dir. of Survey
Downstream
Length Surveyed
404.6 ft.
Total Length
404.6 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
243
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
251
Pipe schematic from manhole 32 0115 to 32 0114
MH: 32 0115MH: 32 0114downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01150 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.3 ft. MGO - General Observation - MAG COATING THROUGHOUT 75%158.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"379.9 ft. RFB - Roots Fine Barrell, from 09 to 03 o'clock, within 8 inches of joint: YES, Start399.9 ft. RFB - Roots Fine Barrell, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish404.6 ft. AMH - Downstream Manhole, Survey Ends - 32 0114404.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK404.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Barrell, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    379.9 ft. - Roots Fine Barrell, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
404.6AMH32 0114
0AMH32 0115
404.6MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWL
17.3MGOMAG COATING THROUGHOUT 75%
0MWM
379.9RFB
399.9RFB
0MGOCOCKROACHES IN MANHOLE
404.6SAV
158.5TF
2SAV

Properties (5)

additional_info
SC364776
customer
LACSD
datetime
2018-07-18T03:11:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false