Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2018, 09:55 AM
  • 32 0116_32 0115A_08202018_025719.mp4

Date
08/20/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P25901
Time
2:55 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6006
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
32 0116
Downstream MH
32 0115A
Dir. of Survey
Downstream
Length Surveyed
284.9 ft.
Total Length
284.9 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
126
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
126
Pipe schematic from manhole 32 0116 to 32 0115A
MH: 32 0116MH: 32 0115Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MGO - General Observation - MAG COATING THROUGHOUT 90%0 ft. AMH - Upstream Manhole, Survey Begins - 32 011674.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start283.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish284.9 ft. AMH - Downstream Manhole, Survey Ends - 32 0115A284.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    74.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
284.9AMH32 0115A
0MWL
0MWM
74.7SAV
0MGOMAG COATING THROUGHOUT 90%
284.9MGOACTIVE CONNECTION AT MH 9 O'CLOCK
283.1SAV
0AMH32 0116

Properties (5)

additional_info
SC364776
customer
LACSD
datetime
2018-08-20T02:55:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false