Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2018, 07:26 AM
  • 32 0151_32 0150A_07262018_002926.mp4

Date
07/26/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19902
Time
12:26 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5881
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0151
Downstream MH
32 0150A
Dir. of Survey
Downstream
Length Surveyed
296 ft.
Total Length
296 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
3
Overall Quick
Overall Rating
290
Pipe schematic from manhole 32 0151 to 32 0150A
MH: 32 0151MH: 32 0150Adownstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01510 ft. MGO - General Observation - MAG COATING THROUGHOUT 60%0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start78.9 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"294.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish296 ft. MGO - General Observation - COCKROACHES IN MANHOLE296 ft. AMH - Downstream Manhole, Survey Ends - 32 0150A296 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    296 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
294.3SAP
0MWL
0AMH32 0151
0MGOMAG COATING THROUGHOUT 60%
294.3DAGS
2DAGS
296MGOCOCKROACHES IN MANHOLE
296AMH32 0150A
2SAP
0MGOCOCKROACHES IN MANHOLE
296MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
78.9TBA
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC359779
custom_field_two
2
customer
LACSD
datetime
2018-07-26T00:26:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false