Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2018, 08:18 AM
  • 32 0159_32 0158_07252018_012246.mp4

Date
07/25/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19911
Time
1:18 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5880
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0159
Downstream MH
32 0158
Dir. of Survey
Downstream
Length Surveyed
429.1 ft.
Total Length
429.1 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
255
O&M Index
2
O&M Quick
2P00
O&M Rating
170
Overall Index
3
Overall Quick
Overall Rating
425
Pipe schematic from manhole 32 0159 to 32 0158
MH: 32 0159MH: 32 0158downstream0 ft. MGO - General Observation - MAG COATING 75%0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01590 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start427.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish427.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE427.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish429.1 ft. AMH - Downstream Manhole, Survey Ends - 32 0158

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    427.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0MGOMAG COATING 75%
427.6SAP
0MWL
2SAP
2DAGS
427.6MGOCOCKROACHES IN MANHOLE
427.6DAGS
0AMH32 0159
429.1AMH32 0158
0MWM

Properties (6)

additional_info
SC359748
custom_field_two
2
customer
LACSD
datetime
2018-07-25T01:18:49-07:00
documentation
PRO PIPE
is_lateral_inspection
false