Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2018, 06:59 AM
  • 32 0154_32 0153 _07252018_235720.mp4

Date
07/25/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19905
Time
11:59 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5881
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0154
Downstream MH
32 0153
Dir. of Survey
Downstream
Length Surveyed
426.1 ft.
Total Length
426.1 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
255
O&M Index
2
O&M Quick
412P
O&M Rating
174
Overall Index
3
Overall Quick
Overall Rating
429
Pipe schematic from manhole 32 0154 to 32 0153
MH: 32 0154MH: 32 0153downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - MAG COATING 65%0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01542 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start424.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE424.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish424.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish426.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK426.1 ft. AMH - Downstream Manhole, Survey Ends - 32 0153

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    424.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
426.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
424.6MGOCOCKROACHES IN MANHOLE
0MWL
424.6SAP
2SAP
426.1AMH32 0153
0MGOMAG COATING 65%
2DAGS
0MWM
0AMH32 0154
424.6DAGS

Properties (6)

additional_info
SC359749
custom_field_two
2
customer
LACSD
datetime
2018-07-25T23:59:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false