Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2018, 09:01 AM
  • 32 0112A_32 0112 _08242018_020149.mp4

Date
08/24/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19858
Time
2:01 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6017
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
32 0112A
Downstream MH
32 0112
Dir. of Survey
Downstream
Length Surveyed
95.7 ft.
Total Length
95.7 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
54
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
2
Overall Quick
Overall Rating
92
Pipe schematic from manhole 32 0112A to 32 0112
MH: 32 0112AMH: 32 0112downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 0112A0 ft. MWM - Water Mark, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start4.4 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start95.7 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish95.7 ft. AMH - Downstream Manhole, Survey Ends - 32 011295.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Upstream Manhole, Survey Begins - 32 0112A

    0 ft. - Upstream Manhole, Survey Begins - 32 0112A

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2DAGS
4.4SAV
95.7SAV
95.7AMH32 0112
95.7DAGS
0MWL
0AMH32 0112A
0MWM

Properties (6)

additional_info
SC364781
custom_field_two
2
customer
LACSD
datetime
2018-08-24T02:01:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false