Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2018, 09:28 AM
  • 32 0157_32 0185 _07252018_022909.mp4

Date
07/25/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19909
Time
2:28 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5880
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0157
Downstream MH
32 0185
Dir. of Survey
Downstream
Length Surveyed
159.5 ft.
Total Length
159.5 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
93
O&M Index
2
O&M Quick
3A2E
O&M Rating
95
Overall Index
3
Overall Quick
Overall Rating
188
Pipe schematic from manhole 32 0157 to 32 0185
MH: 32 0157MH: 32 0185downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01570 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start100.2 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS157.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish157.5 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish157.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish159.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK159.5 ft. AMH - Downstream Manhole, Survey Ends - 32 0185159.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    159.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
2SAP
159.5MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH32 0157
100.2DSZDEBRIS
159.5AMH32 0185
157.5DSZ
0MWM
0MWL
157.5SAP
159.5MGOCOCKROACHES IN MANHOLE
2DAGS
157.5DAGS

Properties (6)

additional_info
SC359748
custom_field_two
2
customer
LACSD
datetime
2018-07-25T02:28:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false