Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2018, 10:21 AM
  • 32 0121_32 0120_08012018_032121.mp4

Date
08/01/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19866
Time
3:21 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5886
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
32 0121
Downstream MH
32 0120
Dir. of Survey
Downstream
Length Surveyed
537.8 ft.
Total Length
537.8 ft.
Structural Index
3
Structural Quick
3T00
Structural Rating
321
O&M Index
2
O&M Quick
2T00
O&M Rating
214
Overall Index
3
Overall Quick
Overall Rating
535
Pipe schematic from manhole 32 0121 to 32 0120
MH: 32 0121MH: 32 0120downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01210 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - MAG COATING THROUGHOUT 60%2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start536.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish536.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish537 ft. MGO - General Observation - COCKROACHES IN MANHOLE537.8 ft. AMH - Downstream Manhole, Survey Ends - 32 0120537.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOC

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2SAV
0MWL
2DAGS
537.8AMH32 0120
536.9DAGS
0AMH32 0121
537.8MGOACTIVE CONNECTION AT MH 9 O'CLOC
536.9SAV
0MWM
537MGOCOCKROACHES IN MANHOLE
0MGOMAG COATING THROUGHOUT 60%

Properties (6)

additional_info
SC364754
custom_field_two
3
customer
LACSD
datetime
2018-08-01T03:21:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false