Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2018, 08:40 AM
  • 32 0147_32 0146 _07262018_014046.mp4

Date
07/26/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19896
Time
1:40 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5881
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0147
Downstream MH
32 0146
Dir. of Survey
Downstream
Length Surveyed
456.5 ft.
Total Length
456.5 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
273
O&M Index
2
O&M Quick
412Q
O&M Rating
186
Overall Index
3
Overall Quick
Overall Rating
459
Pipe schematic from manhole 32 0147 to 32 0146
MH: 32 0147MH: 32 0146downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01472 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start455.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish455.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish456.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE456.5 ft. AMH - Downstream Manhole, Survey Ends - 32 0146

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    456.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (9)

DistanceCodeObservation
2DAGS
0MWM
0MWL
456.5MGOCOCKROACHES IN MANHOLE
0AMH32 0147
456.5AMH32 0146
455.4SAP
455.4DAGS
2SAP

Properties (6)

additional_info
SC359749
custom_field_two
2
customer
LACSD
datetime
2018-07-26T01:40:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false