Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2018, 07:18 AM
  • 32 0153_32 0152 _07262018_001927.mp4

Date
07/26/2018
W/O
718360
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19904
Time
12:18 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5881
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
13
Purpose
Routine Assessment
Project
WO_718360_TV32015_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0153
Downstream MH
32 0152
Dir. of Survey
Downstream
Length Surveyed
109.2 ft.
Total Length
109.2 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
63
O&M Index
2
O&M Quick
412C
O&M Rating
46
Overall Index
3
Overall Quick
Overall Rating
109
Pipe schematic from manhole 32 0153 to 32 0152
MH: 32 0153MH: 32 0152downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01530 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - MAG COATING THROUGHOUT 65%2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start107.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish107.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish109.2 ft. AMH - Downstream Manhole, Survey Ends - 32 0152

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Downstream Manhole, Survey Ends - 32 0152

    109.2 ft. - Downstream Manhole, Survey Ends - 32 0152

Observations (11)

DistanceCodeObservation
0AMH32 0153
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
109.2AMH32 0152
107.5SAP
2SAP
3.6DAGS
0MWL
0MWM
0MGOMAG COATING THROUGHOUT 65%
107.5DAGS

Properties (6)

additional_info
SC359749
custom_field_two
2
customer
LACSD
datetime
2018-07-26T00:18:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false