Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2018, 10:28 AM
  • 02 0301_02 0300 _12172018_022856.mp4

Date
12/17/2018
W/O
740647
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P02615
Time
2:28 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6275
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22A
Purpose
Routine Assessment
Project
RFIR_WO_740647_TV02381_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0301
Downstream MH
02 0300
Dir. of Survey
Downstream
Length Surveyed
152.1 ft.
Total Length
152.1 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
90
O&M Index
2
O&M Quick
412E
O&M Rating
64
Overall Index
3
Overall Quick
Overall Rating
154
Pipe schematic from manhole 02 0301 to 02 0300
MH: 02 0301MH: 02 0300downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 03010 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start151.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish151.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish152.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0300

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
151.6CM
2DAGS
0MWM
151.6DAGS
152.1AMH02 0300
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH02 0301
2CM
0MWL

Properties (6)

additional_info
SC365391
custom_field_two
3
customer
LACSD
datetime
2018-12-17T02:28:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false