Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2018, 10:58 AM
  • 02 2442_02 2441 _12202018_031358.mp4

Date
12/20/2018
W/O
740647
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P26321
Time
2:58 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6278
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_740647_TV02381_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 2441
Downstream MH
02 2442
Dir. of Survey
Upstream
Length Surveyed
92.4 ft.
Total Length
92.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412C
O&M Rating
40
Overall Index
2
Overall Quick
Overall Rating
40
Pipe schematic from manhole 02 2441 to 02 2442
MH: 02 2441MH: 02 2442upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 02 24420.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish90.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start92.4 ft. MWM - Water Mark, 60 %of cross sectional area92.4 ft. MWL - Water Level, 15 %of cross sectional area92.4 ft. AMH - Downstream Manhole, Survey Begins - 02 2441

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
92.2DAGS
2DAGS
0MWM
0MWL
0AMH02 2441
92.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK
92.4AMH02 2442

Properties (7)

additional_info
SC365394
custom_field_two
3
customer
LACSD
datetime
2018-12-20T02:58:14-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40723