Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2018, 10:00 AM
  • 02 2439_02 2438 _12202018_020042.mp4

Date
12/20/2018
W/O
740647
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P26318
Time
2:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6278
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_740647_TV02381_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 2439
Downstream MH
02 2438
Dir. of Survey
Downstream
Length Surveyed
181.7 ft.
Total Length
181.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
512H
O&M Rating
95
Overall Index
2
Overall Quick
Overall Rating
95
Pipe schematic from manhole 02 2439 to 02 2438
MH: 02 2439MH: 02 2438downstream0 ft. MWM - Water Mark, 75 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 24390 ft. MWL - Water Level, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start128.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start178.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Finish178.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Finish181.7 ft. AMH - Downstream Manhole, Survey Ends - 02 2438181.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock,  , within 8 inches of joint: YES, Start

    128.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
178.6DAGS
178.6DAE
0MWM
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
181.7AMH02 2438
128.5DAE
0AMH02 2439
181.7MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWL
2DAGS

Properties (7)

additional_info
SC365394
custom_field_two
3
customer
LACSD
datetime
2018-12-20T02:00:34-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40723