Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2018, 07:42 AM
  • 02 0283_02 0282 _12172018_234307.mp4

Date
12/17/2018
W/O
740647
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P02597
Time
11:42 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6276
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_740647_TV02381_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0283
Downstream MH
02 0282
Dir. of Survey
Downstream
Length Surveyed
283 ft.
Total Length
283 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
168
O&M Index
2
O&M Quick
412J
O&M Rating
116
Overall Index
3
Overall Quick
Overall Rating
284
Pipe schematic from manhole 02 0283 to 02 0282
MH: 02 0283MH: 02 0282downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 02830 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start33.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"180.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"259.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"282 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish282 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish283 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK283 ft. AMH - Downstream Manhole, Survey Ends - 02 0282283 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    283 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
0AMH02 0283
282DAGS
283MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL
283AMH02 0282
33.9TF
180.3TFC
0MWM
2DAGS
283MGOCOCKROACHES IN MANHOLE
259.6TFC
2CM
282CM

Properties (6)

additional_info
SC365392
custom_field_two
3
customer
LACSD
datetime
2018-12-17T23:42:31-08:00
documentation
PRO PIPE
is_lateral_inspection
false