Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 14, 2018, 10:18 AM
  • 02 0311_02 0310 _12142018_021901.mp4

Date
12/14/2018
W/O
740647
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P02625
Time
2:18 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6274
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_740647_TV02381_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0311
Downstream MH
02 0310
Dir. of Survey
Downstream
Length Surveyed
93.4 ft.
Total Length
93.4 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
48
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
2
Overall Quick
Overall Rating
84
Pipe schematic from manhole 02 0311 to 02 0310
MH: 02 0311MH: 02 0310downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03112 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK91.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish91.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish93.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE93.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0310

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    93.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
2DAGS
93.4MGOCOCKROACHES IN MANHOLE
91.3MGOACTIVE CONNECTION AT MH 3 O'CLOCK
10CM
93.4AMH02 0310
0MWL
0MWM
91.3DAGS
61.2TFC
91.3CM
0AMH02 0311

Properties (6)

additional_info
SC365390
custom_field_two
3
customer
LACSD
datetime
2018-12-14T02:18:43-08:00
documentation
PRO PIPE
is_lateral_inspection
false