Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2018, 06:37 AM
  • 02 0266_02 0265 _12192018_223759.mp4

Date
12/19/2018
W/O
740647
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P02580
Time
10:37 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6278
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_740647_TV02381_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0266
Downstream MH
02 0265
Dir. of Survey
Downstream
Length Surveyed
284.8 ft.
Total Length
284.8 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
2
O&M Quick
2J11
O&M Rating
113
Overall Index
2
Overall Quick
Overall Rating
278
Pipe schematic from manhole 02 0266 to 02 0265
MH: 02 0266MH: 02 0265downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 02660 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start46.9 ft. RFL - Roots Fine Lateral, at 12 o'clock46.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"75.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"102.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"124.4 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"220.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"283.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish283.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish284.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0265

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"

    46.9 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6", 6"

Observations (14)

DistanceCodeObservation
283.4CM
283.4DAGS
220.4TFA
2DAGS
10CM
46.9RFL
102.4TF
0MWL
46.9TFA
75.9TBA
0AMH02 0266
0MWM
284.8AMH02 0265
124.4TBA

Properties (6)

additional_info
SC365394
custom_field_two
3
customer
LACSD
datetime
2018-12-19T22:37:13-08:00
documentation
PRO PIPE
is_lateral_inspection
false