Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2018, 07:47 AM
  • 02 0267_02 2438 _12192018_234757.mp4

Date
12/19/2018
W/O
740647
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00251
PipeID
P26322
Time
11:47 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6278
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_740647_TV02381_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 2438
Downstream MH
02 0267
Dir. of Survey
Upstream
Length Surveyed
8.3 ft.
Total Length
8.3 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
3
O&M Quick
5122
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 02 2438 to 02 0267
MH: 02 2438MH: 02 0267upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish0 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 02 02674.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start6.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start8.3 ft. MWM - Water Mark, 75 %of cross sectional area8.3 ft. MWL - Water Level, 60 %of cross sectional area8.3 ft. AMH - Downstream Manhole, Survey Begins - 02 2438

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWM
4.2CM
8.3MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL
8.3DAGS
2DAGS
8.3CM
0AMH02 2438
8.3AMH02 0267