Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2019, 08:55 AM
  • 18 0411_18 0410_03192019_020639.mp4

Date
03/19/2019
W/O
756007
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00699
PipeID
P14246
Time
1:55 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6482
Sewer Name
18 SANTA FE STREET RELIEF TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_756007_TV18173_MAR2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0410
Downstream MH
18 0411
Dir. of Survey
Upstream
Length Surveyed
130.2 ft.
Total Length
130.2 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
72
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
76
Pipe schematic from manhole 18 0410 to 18 0411
MH: 18 0410MH: 18 0411upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 04115.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish124.2 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE124.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start130.2 ft. AMH - Downstream Manhole, Survey Begins - 18 0410130.2 ft. MWL - Water Level, 50 %of cross sectional area130.2 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (2)

  • General Observation - MAG COAT THROUGHOUT PIPE

    6 ft. - General Observation - MAG COAT THROUGHOUT PIPE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
124.9SAP
0AMH18 0410
6MGOMAG COAT THROUGHOUT PIPE
130.2AMH18 0411
0MWL
6SAP
0MWM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-19T01:55:55-07:00
documentation
PROPIPE
is_lateral_inspection
false