Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2019, 08:21 AM
  • H 1296_H 1295 _01112019_003757.mp4

Date
01/11/2019
W/O
745550
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01183
PipeID
P17312
Time
12:21 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6301
Sewer Name
H JOINT OUTFALL H - UNIT 8L
City
AZUSA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
`
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_745550_TV22154_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
H 1295
Downstream MH
H 1296
Dir. of Survey
Upstream
Length Surveyed
407.7 ft.
Total Length
407.7 ft.
Structural Index
2
Structural Quick
2O00
Structural Rating
160
O&M Index
2
O&M Quick
2O00
O&M Rating
162
Overall Index
2
Overall Quick
Overall Rating
322
Pipe schematic from manhole H 1295 to H 1296
MH: H 1295MH: H 1296upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 12960 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK1.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish1.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish402.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start405.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start407.7 ft. AMH - Downstream Manhole, Survey Begins - H 1295407.7 ft. MWL - Water Level, 10 %of cross sectional area407.7 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    407.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0AMHH 1295
4.9SSS
0MWL
407.7AMHH 1296
407.7MGOCOCKROACHES IN MANHOLE
0MWM
406.2DAGS
407.7MGOACTIVE CONNECTION AT MH 9 O'CLOCK
2DAGS
406.2SSS

Properties (6)

additional_info
SC365667
custom_field_two
2
customer
LACSD
datetime
2019-01-11T00:21:39-08:00
documentation
PRO PIPE
is_lateral_inspection
false