Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 2, 2019, 09:31 AM
  • D 0109_D 0108 _01022019_015527.mp4

Date
01/02/2019
W/O
740289
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10015
Time
1:31 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6308
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_740259_TV05172_DEC2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
D 0109
Downstream MH
D 0108
Dir. of Survey
Downstream
Length Surveyed
550.4 ft.
Total Length
550.4 ft.
Structural Index
3
Structural Quick
3U2U
Structural Rating
548
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
548
Pipe schematic from manhole D 0109 to D 0108
MH: D 0109MH: D 0108downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - D 01092.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start548.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish550.4 ft. AMH - Downstream Manhole, Survey Ends - D 0108550.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK550.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK550.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
550.4AMHD 0108
0MWM
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
2.1SSS
0AMHD 0109
548.3SSS
550.4MGOCONNECTION AT MH 3 O'CLOCK
550.4MGOCONNECTION AT MH 9 O'CLOCK
550.4SAP
2.1SAP

Properties (6)

additional_info
SC365492
custom_field_two
2
customer
LACSD
datetime
2019-01-02T01:31:48-08:00
documentation
PROPIPE
is_lateral_inspection
false