Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2019, 11:15 AM
  • Section#4_30 0240_30 0239__5232019__I0148.mp4

Date
05/23/2019
W/O
0771073
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00884
PipeID
P17941
Time
4:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0148
Sewer Name
30 VIA CAMPESINA TRUNK
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
09
Purpose
Routine Assessment
Project
20190523MDM_VIA_CAMPESINA_TRUNK
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
30 0240
Downstream MH
30 0239
Dir. of Survey
Downstream
Length Surveyed
71.9 ft.
Total Length
71.9 ft.
Structural Index
3
Structural Quick
4B27
Structural Rating
74
O&M Index
3
O&M Quick
3911
O&M Rating
28
Overall Index
3
Overall Quick
Overall Rating
102
Pipe schematic from manhole 30 0240 to 30 0239
MH: 30 0240MH: 30 0239downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. SAM - Surface Aggregate Missing, from 05 to 07 o'clock, within 8 inches of joint: NO - BOTTOM OF PIPE CORRODED INSDE MH0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2.9 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YESR - 4%6.3 ft. RMJ - Roots Medium Joint, from 03 to 06 o'clock, 5 %, within 8 inches of joint: YESR7.6 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 25 %, within 8 inches of joint: YESR12.5 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR17.2 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR21.1 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR32.9 ft. RMJ - Roots Medium Joint, from 03 to 06 o'clock, 5 %, within 8 inches of joint: YESR34.4 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELNG CONCRETE SEVERE AGG ATT ACHED41.1 ft. RMJ - Roots Medium Joint, from 12 to 06 o'clock, 15 %, within 8 inches of joint: YESR45.5 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 10 %, within 8 inches of joint: YESR51.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN63.1 ft. RMJ - Roots Medium Joint, from 04 to 08 o'clock, 5 %, within 8 inches of joint: YESR71.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED71.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG71.9 ft. AMH - Downstream Manhole, Survey Ends - 4:40AM

Observation photos (5)

  • Surface Aggregate Missing, from 05 to 07 o'clock, within 8 inches of joint: NO - BOTTOM OF PIPE CORRODED INSDE MH

    0 ft. - Surface Aggregate Missing, from 05 to 07 o'clock, within 8 inches of joint: NO - BOTTOM OF PIPE CORRODED INSDE MH

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Roots Medium Joint, from 07 to 05 o'clock, 25 %, within 8 inches of joint: YESR

    7.6 ft. - Roots Medium Joint, from 07 to 05 o'clock, 25 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR

    21.1 ft. - Roots Medium Joint, from 07 to 05 o'clock, 10 %, within 8 inches of joint: YESR

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELNG CONCRETE SEVERE AGG ATT ACHED

    34.4 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELNG CONCRETE SEVERE AGG ATT ACHED

Observations (20)

DistanceCodeObservation
41.1RMJ
17.2RMJ
34.4SSSBLISTERING PEELNG CONCRETE SEVERE AGG ATT ACHED
0MWL
45.5RMJ
0SAMBOTTOM OF PIPE CORRODED INSDE MH
71.9AMH4:40AM
63.1RMJ
7.6RMJ
2SAMSEVERE AGG
6.3RMJ
71.3SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
0AMH4:20AM
2.9RFJ4%
21.1RMJ
71.3SAMSEVERE AGG
32.9RMJ
0MWM
51.3TFOPEN
12.5RMJ

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2019-05-23T04:15:00-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false