Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2019, 06:44 PM
  • 18 0437_18 0436_5212019_114917.mp4

Date
05/21/2019
W/O
0767446
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00675
PipeID
P14287
Time
11:44 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
G7984
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTE FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Maintenance Related
Project
20190521DF_FLORENCE_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
18 0437
Downstream MH
18 0436
Dir. of Survey
Downstream
Length Surveyed
403.8 ft.
Total Length
403.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0437 to 18 0436
MH: 18 0437MH: 18 0436downstream0 ft. AMH - Upstream Manhole, Survey Begins - 11:45 AM0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"53.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"77.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"101.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"125.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"155.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"178.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"202.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"230.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"255.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"279.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"303.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open327.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open355.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"375.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"401.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish403.8 ft. AMH - Downstream Manhole, Survey Ends - 12:09 PM403.8 ft. MGO - General Observation - Grease Throughout The Reach (5%)

Observations (23)

DistanceCodeObservation
375.8TFC
125.7TFC
230.6TFC
327.7TFOpen
255.2TFC
0AMH11:45 AM
101.7TFC
403.8AMH12:09 PM
279.2TFC
155.5TFC
403.8MGOGrease Throughout The Reach (5%)
2MGOConn. @ Mh, 9 O' Clock. Active
8.4TFC
401.4SAV
77.1TFC
53.3TFC
178.1TFC
0MWL
355.7TFC
303.5TFOpen
0MWM
2SAV
202.5TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-05-21T11:44:15-07:00
documentation
FRANKLIN, BRAR, CASTILLO
is_lateral_inspection
false