Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 19, 2018, 08:59 AM
  • 05 0136_05 0135 _12192018_011809.mp4

Date
12/19/2018
W/O
740131
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05427
Time
12:59 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6252
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_740015_TV05147_DEC2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
05 0135
Downstream MH
05 0136
Dir. of Survey
Upstream
Length Surveyed
196.4 ft.
Total Length
196.4 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
117
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
117
Pipe schematic from manhole 05 0135 to 05 0136
MH: 05 0135MH: 05 0136upstream0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 05 0136194.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start194.3 ft. MGO - General Observation - MAG COAT196.4 ft. MWM - Water Mark, 5 %of cross sectional area196.4 ft. AMH - Downstream Manhole, Survey Begins - 05 0135196.4 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
196.4SAP
2.1SAP
0MWM
0AMH05 0135
0MWL
2.1MGOMAG COAT
196.4MGOCONNECTION AT MH 3 O'CLOCK
196.4AMH05 0136

Properties (5)

additional_info
SC365485
custom_field_two
2
customer
LACSD
datetime
2018-12-19T00:59:33-08:00
is_lateral_inspection
false