Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2018, 06:50 AM
  • 05 0104_05 0103 _12172018_230241.mp4

Date
12/17/2018
W/O
740131
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05394
Time
10:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6251
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_740015_TV05147_DEC2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
05 0104
Downstream MH
05 0103
Dir. of Survey
Downstream
Length Surveyed
332.8 ft.
Total Length
332.8 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
198
Pipe schematic from manhole 05 0104 to 05 0103
MH: 05 0104MH: 05 0103downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 01040 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. MGO - General Observation - MAG COAT332.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish332.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0103

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMH05 0104
2.8SAP
0MWL
332.5SAP
332.8AMH05 0103
2.8MGOMAG COAT
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (5)

additional_info
SC365484
custom_field_two
2
customer
LACSD
datetime
2018-12-17T22:50:00-08:00
is_lateral_inspection
false