Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2018, 10:53 AM
  • 05 0151_05 0150 _12122018_032635.mp4

Date
12/12/2018
W/O
740131
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05443
Time
2:53 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6247
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_740015_TV05147_DEC2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
05 0151
Downstream MH
05 0150
Dir. of Survey
Downstream
Length Surveyed
303.3 ft.
Total Length
303.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 05 0151 to 05 0150
MH: 05 0151MH: 05 0150downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 01510 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.7 ft. MGO - General Observation - HEAVY STEAM299.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish303.3 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT303.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0150303.3 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWM
2.1SAP
19.7MGOHEAVY STEAM
0MWL
0AMH05 0151
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
303.3MGOCAPPED CONNECTION AT 9 O' CLOCK AT
303.3AMH05 0150
303.3MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
299.2SAP

Properties (5)

additional_info
SC365480
custom_field_two
2
customer
LACSD
datetime
2018-12-12T02:53:13-08:00
is_lateral_inspection
false