Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 13, 2018, 11:09 AM
  • 05 0143_05 0142 _12132018_031841.mp4

Date
12/13/2018
W/O
740131
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05435
Time
3:09 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6248
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_740015_TV05147_DEC2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
05 0143
Downstream MH
05 0142
Dir. of Survey
Downstream
Length Surveyed
175.3 ft.
Total Length
175.3 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
105
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
105
Pipe schematic from manhole 05 0143 to 05 0142
MH: 05 0143MH: 05 0142downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 01432.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT175.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish175.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0142 ZOOMED IN

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2.1SAP
175.3SAP
0MGOCONNECTION AT MH 3 O'CLOCK
2.1MGOMAG COAT
175.3AMH05 0142 ZOOMED IN
0MWL
0MWM
0AMH05 0143

Properties (5)

additional_info
SC365481
custom_field_two
2
customer
LACSD
datetime
2018-12-13T03:09:03-08:00
is_lateral_inspection
false