Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2019, 11:18 AM
  • 18 0495_18 0494 _01302019_034531.mp4

Date
01/30/2019
W/O
745525
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00691
PipeID
P14349
Time
3:18 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6372
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
WO_18099_TV745525_JAN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
18 0495
Downstream MH
18 0494
Dir. of Survey
Downstream
Length Surveyed
631.6 ft.
Total Length
631.6 ft.
Structural Index
4
Structural Quick
534S
Structural Rating
420
O&M Index
1
O&M Quick
2114
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
426
Pipe schematic from manhole 18 0495 to 18 0494
MH: 18 0495MH: 18 0494downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04950 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK18.5 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES21.8 ft. B - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES - APPEARS REPAIRED31.3 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES54.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES72.2 ft. B - Broken, from 01 to 03 o'clock, within 8 inches of joint: YES95.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES118.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES146.2 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES151.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start156.7 ft. MMC - Material Change, Cast Iron156.7 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES159.7 ft. MMC - Material Change, Vitrified clay pipe180.1 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES256.9 ft. RFJ - Roots Fine Joint, at 01 o'clock, within 8 inches of joint: YES281.8 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 8", 1"291 ft. RFJ - Roots Fine Joint, from 08 to 11 o'clock, within 8 inches of joint: YES350.7 ft. B - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES438.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"450.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"629.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish631.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0494

Observation photos (9)

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    18.5 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Broken, from 01 to 03 o'clock, within 8 inches of joint: YES

    72.2 ft. - Broken, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    95.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    118.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    151.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 09 to 03 o'clock, within 8 inches of joint: YES

    156.7 ft. - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

    180.1 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 11 o'clock, within 8 inches of joint: YES

    291 ft. - Roots Fine Joint, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

    350.7 ft. - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
629.2FM
0AMH18 0495
95.3FM
18.5FM
21.8BAPPEARS REPAIRED
118.4CL
350.7B
631.6AMH18 0494
0MGOCONNECTION AT MH 9 OCLOCK
450.4TB
281.8TBI
0MGOCONNECTION AT MH 3 OCLOCK
54.5CM
156.7MMC
156.7B
438.9TBA
256.9RFJ
72.2B
159.7MMC
146.2RFJ
291RFJ
31.3FM
180.1RFJ
151.6FM

Properties (4)

custom_field_two
1
customer
LACSD
datetime
2019-01-30T03:18:16-08:00
is_lateral_inspection
false