Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2019, 09:23 AM
  • 01 0518_01 0517_01072019_013928.mp4

Date
01/07/2019
W/O
740024
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00206
PipeID
P01002
Time
1:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6314
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_740024_TV01017_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0518
Downstream MH
01 0517
Dir. of Survey
Downstream
Length Surveyed
315.2 ft.
Total Length
315.2 ft.
Structural Index
3
Structural Quick
514B
Structural Rating
217
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
222
Pipe schematic from manhole 01 0518 to 01 0517
MH: 01 0518MH: 01 0517downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05182.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES76.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.5 ft. B - Broken, from 09 to 11 o'clock, within 8 inches of joint: YES99.6 ft. RFB - Roots Fine Barrell, at 11 o'clock100.5 ft. RML - Roots Medium Lateral, at 10 o'clock, 25 %, within 8 inches of joint: NO100.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.7 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES151.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES228.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"252.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256.3 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES262.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish262.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start279 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"303 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"311.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"315.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish315.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0517

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

    75.1 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Broken, from 09 to 11 o'clock, within 8 inches of joint: YES

    99.5 ft. - Broken, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Barrell, at 11 o'clock

    99.6 ft. - Roots Fine Barrell, at 11 o'clock

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    146.7 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    209.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    256.3 ft. - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    262.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (30)

DistanceCodeObservation
252.5TFC
279TFC
133.4TFC
256.3FC
311.5TF
209.3FM
315.2FM
75.1FC
146.7FM
178.4TFC
262.1CM
303TFC
0MGOCONNECTION AT MH 3 O'CLOCK
315.2AMH01 0517
0MWM
262.1FM
100.5RML
99.5B
67.5TF
151.5TFC
2.4CM
196.4TF
0MWL
100.5TF
99.6RFB
228.7TFC
76.8TFC
202.1TFC
249.4TFC
0AMH01 0518

Properties (5)

additional_info
SC365498
custom_field_two
2
customer
LACSD
datetime
2019-01-07T01:23:30-08:00
is_lateral_inspection
false