Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2019, 04:34 AM
  • 29 0341_29 0340 _03252019_222131.mp4

Date
03/25/2019
W/O
755793
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z01017
PipeID
P24361
Time
9:34 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6494
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_755793_TV29085_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0341
Downstream MH
29 0340
Dir. of Survey
Downstream
Length Surveyed
251.8 ft.
Total Length
251.8 ft.
Structural Index
4
Structural Quick
4932
Structural Rating
44
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
44
Pipe schematic from manhole 29 0341 to 29 0340
MH: 29 0341MH: 29 0340downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 03416.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES19.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES25.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"67.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish75.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"75.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES75.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES85.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES100 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES107.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"133.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"140.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES161.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES166 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"168 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES168.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"179.9 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES185.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start216.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"224 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"250.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish251.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0340

Observation photos (12)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    19.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    25.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    75.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    75.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    85.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    100 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    140.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    161.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    168 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    179.9 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    185.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
75.5CM
185.7FM
216.1TFC
44.5TFC
251.8AMH29 0340
100CM
85.2FM
19.1FM
168FM
0MWM
75.2TFA
0MWL
250.6FM
133.2TFC
140.9FM
161.6FM
107.3TFA
25.4FM
168.9TFC
224TFA
6.4FM
179.9FM
0AMH29 0341
166TFA
75.2CL
67.7FM

Properties (3)

customer
LACSD
datetime
2019-03-25T21:34:01-07:00
is_lateral_inspection
false