Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2019, 06:07 AM
  • 29 0342_29 0341 _03252019_234219.mp4

Date
03/25/2019
W/O
755793
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z01017
PipeID
P24362
Time
11:07 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6494
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_755793_TV29085_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0341
Downstream MH
29 0342
Dir. of Survey
Upstream
Length Surveyed
314.7 ft.
Total Length
314.7 ft.
Structural Index
3
Structural Quick
3322
Structural Rating
13
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 29 0341 to 29 0342
MH: 29 0341MH: 29 0342upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 03427.6 ft. FC - Fracture Circumferential, from 12 to 12 o'clock, within 8 inches of joint: YES17.7 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: YES, 8"23.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"56.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"116 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"121.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"135.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES148.4 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 8", 1"181.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"220.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish223 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"240.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"247.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"269.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start280.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES298.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES298.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"314.7 ft. MWM - Water Mark, 25 %of cross sectional area314.7 ft. MWL - Water Level, 5 %of cross sectional area314.7 ft. AMH - Downstream Manhole, Survey Begins - 29 0341

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    16.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    34 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    45.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 8", 1"

    166.3 ft. - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 8", 1"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    179.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 12 to 12 o'clock, within 8 inches of joint: YES

    307.1 ft. - Fracture Circumferential, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
297TFB
307.1FC
258.4TF
291.2TF
91.7TFA
179.6CM
133.4TFC
67.4TBA
193.5TFC
16.4CM
198.7TFC
0MWM
45.5CM
314.7AMH29 0342
0MWL
166.3TBI
94.6CM
74.1TFC
34CL
16.4TFC
0AMH29 0341

Properties (4)

custom_field_two
2
customer
LACSD
datetime
2019-03-25T23:07:52-07:00
is_lateral_inspection
false