Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2019, 09:42 AM
  • B 0633_B 0632 _02062019_015443.mpg

Date
02/06/2019
W/O
745400
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00108
PipeID
P09299
Time
1:42 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6264
Sewer Name
B JOINT OUTFALL B - UNIT 8E
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_745400_TV15229_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 0633
Downstream MH
B 0632
Dir. of Survey
Downstream
Length Surveyed
280.2 ft.
Total Length
280.2 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole B 0633 to B 0632
MH: B 0633MH: B 0632downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 06330 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK3.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.4 ft. MGO - General Observation - MAG COAT277.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish280.2 ft. AMH - Downstream Manhole, Survey Ends - B 0632

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
280.2AMHB 0632
277.5SAP
0MWL
3.4SAP
0AMHB 0633
0MGOCONNECTION AT MH 9 OCLOCK
3.4MGOMAG COAT
0MWM
0MGOCONNECTION AT MH 3 OCLOCK

Properties (4)

custom_field_two
2
customer
LACSD
datetime
2019-02-06T01:42:53-08:00
is_lateral_inspection
false