Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2019, 09:31 AM
  • B 0634_B 0633 _02062019_014212.mpg

Date
02/06/2019
W/O
745400
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00108
PipeID
P09300
Time
1:31 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6264
Sewer Name
B JOINT OUTFALL B - UNIT 8E
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_745400_TV15229_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 0634
Downstream MH
B 0633
Dir. of Survey
Downstream
Length Surveyed
270.9 ft.
Total Length
270.9 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
159
Pipe schematic from manhole B 0634 to B 0633
MH: B 0634MH: B 0633downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 06340 ft. MWM - Water Mark, 45 %of cross sectional area2.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.4 ft. MGO - General Observation - MAG COAT267.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish270.9 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK270.9 ft. AMH - Downstream Manhole, Survey Ends - B 0633270.9 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
270.9MGOCONNECTION AT MH 3 OCLOCK
2.4MGOMAG COAT
267.4SAP
0AMHB 0634
2.3SAP
270.9AMHB 0633
270.9MGOCONNECTION AT MH 9 OCLOCK
0MWM

Properties (4)

custom_field_two
2
customer
LACSD
datetime
2019-02-06T01:31:01-08:00
is_lateral_inspection
false