Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 15, 2019, 10:06 AM
  • 18 0439_18 0438_5152019_031729.mp4

Date
05/15/2019
W/O
0767446
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00675
PipeID
P14289
Time
3:06 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H1211
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
20190515MDM_FLORENCE_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
18 0439
Downstream MH
18 0438
Dir. of Survey
Downstream
Length Surveyed
309.9 ft.
Total Length
309.9 ft.
Structural Index
3
Structural Quick
4122
Structural Rating
8
O&M Index
3
O&M Quick
4131
O&M Rating
11
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 18 0439 to 18 0438
MH: 18 0439MH: 18 0438downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:10AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG7.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped27.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped51.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped63.9 ft. MWM - Water Mark, 40 %of cross sectional area75.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped87.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED99.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Finish99.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped99.9 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 06 to 09 o'clock, , within 8 inches of joint: YES, Start128.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped151.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped176 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped199.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped228.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped252.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped276.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped276.7 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 06 to 09 o'clock, , within 8 inches of joint: YES, Finish287.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 06 to 09 o'clock, , within 8 inches of joint: YES, Start300.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped309.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED309.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG309.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active309.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 06 to 09 o'clock, , within 8 inches of joint: YES, Finish309.9 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    87.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Deposits Attached Grease, 20 %of cross sectional area, from 06 to 09 o'clock,  , within 8 inches of joint: YES, Start

    99.9 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 06 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 06 to 09 o'clock,  , within 8 inches of joint: YES, Start

    287.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 06 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (30)

DistanceCodeObservation
309.9AMH3:40AM
228.3TFCCapped
300.7TFCCapped
51.7TFCCapped
309.6SSSPEELING CONCRETE SEVERE AGG ATTACHED
0AMH3:10AM
252.4TFCCapped
176TFCCapped
309.6SAMSEVERE AGG
75.4TFCCapped
0MWM
309.6MGOConn. @ Mh, 3 O' Clock. Active
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
27.5TFCCapped
2DAGS
2SAMSEVERE AGG
151.8TFCCapped
309.6DAGS
276.7TFCCapped
128.5TFCCapped
287.7DAGS
99.9DAGS
0MWL
199.9TFCCapped
63.9MWM
99.9TFCCapped
87.9SSSPEELING CONCRETE SEVERE AGG ATTACHED
7.2TFCCapped
276.7DAGS
99.9DAGS

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2019-05-15T03:06:12-07:00
documentation
MARTIN,REVELES,RUVALCABA
is_lateral_inspection
false