Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 15, 2019, 07:33 AM
  • 18 0441_18 0440_5152019_005404.mp4

Date
05/15/2019
W/O
0767446
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00675
PipeID
P14292
Time
12:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H1211
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
20190515MDM_FLORENCE_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
18 0440
Downstream MH
18 0441
Dir. of Survey
Upstream
Length Surveyed
400.8 ft.
Total Length
400.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 18 0440 to 18 0441
MH: 18 0440MH: 18 0441upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:20AM0.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active5.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped25.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open50 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped74.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped98 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped122.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6" - Capped150.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open174.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped199 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped223 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active247.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped252.4 ft. DAGS - Deposits Attached Grease, 3 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: NO - HARD GREASE OR SCALE275.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped299.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped324 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped348.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped371.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped400.8 ft. MGO - General Observation - POST DEBRIE INSPECTION ONLY400.8 ft. MWM - Water Mark, 60 %of cross sectional area400.8 ft. MWL - Water Level, 10 %of cross sectional area400.8 ft. AMH - Downstream Manhole, Survey Begins - 12:55AM

Observations (23)

DistanceCodeObservation
0MGOPOST DEBRIE INSPECTION ONLY
201.8TFCCapped
0MWM
302.8TFCCapped
395.2TFCCapped
350.8TFCCapped
125.3TFCCapped
148.4DAGSHARD GREASE OR SCALE
226TFCCapped
326.5TFCCapped
153.6TFCCapped
101.3TFCCapped
400.2MGOConn. @ Mh, 3 O' Clock. Active
375.3TFOpen
52.7TFCCapped
400.8AMH1:20AM
29.1TFCCapped
250.6TFOpen
278.2TFCCapped
76.8TFCCapped
0MWL
177.8TFActive
0AMH12:55AM

Properties (5)

additional_info
REVERSE INSPECTION-POST DEBRIE INSPECTION ONLY
customer
LACSD
datetime
2019-05-15T00:33:32-07:00
documentation
MARTIN,REVELES,RUVALCABA
is_lateral_inspection
false