Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2019, 05:00 PM
  • 19 0010_C 0323_5142019_100624.mp4

Date
05/14/2019
W/O
0664155
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00958
PipeID
P21189
Time
10:00 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7978
Sewer Name
A JOA-1A LONG BEACH WRP INFLUENT SWR
City
LONG BEACH
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
11
Purpose
Routine Assessment
Project
20190514DF_JOA_1A_LONG_BEACH_WRP_INFLUENT_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
19 0010
Downstream MH
C 0323
Dir. of Survey
Downstream
Length Surveyed
294 ft.
Total Length
294 ft.
Structural Index
2
Structural Quick
3121
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 19 0010 to C 0323
MH: 19 0010MH: C 0323downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:03 AM0.3 ft. MWL - Water Level, 15 %of cross sectional area0.6 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start108 ft. MGP - General Photograph253.4 ft. CC - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES265.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start294 ft. MSA - Survey Abandoned - HIGH WATER294 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (5)

  • Water Level, 15 %of cross sectional area

    0.3 ft. - Water Level, 15 %of cross sectional area

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph

    108 ft. - General Photograph

  • Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES

    253.4 ft. - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
265.6CM
0AMH10:03 AM
0.3MWL
294MSAHIGH WATER
294SSS
2SSS
108MGP
253.4CC
9DAGS
0.6MWM
294CM
294DAGS

Properties (5)

custom_field_two
5
customer
LACSD
datetime
2019-05-14T10:00:47-07:00
documentation
FRANKLIN, CASTILLO, BRAR
is_lateral_inspection
false