Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2019, 08:08 AM
  • C 0173_C 0172_5132019_012955.mp4

Date
05/13/2019
W/O
0766488
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00130
PipeID
P09697
Time
1:08 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1207
Sewer Name
C JOINT OUTFALL C - UNIT 5C
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190510MDM_JOINT_OUTFALL_C_UNIT_5C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0173
Downstream MH
C 0172
Dir. of Survey
Downstream
Length Surveyed
255.7 ft.
Total Length
255.7 ft.
Structural Index
5
Structural Quick
5742
Structural Rating
45
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
47
Pipe schematic from manhole C 0173 to C 0172
MH: C 0173MH: C 0172downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 1:25AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE8 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR16.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC23.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR45.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR70.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR120.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR145.2 ft. TFI - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 6", 2", 6" - Active239 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG244.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR255.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED255.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE255.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG255.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN255.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active255.7 ft. AMH - Downstream Manhole, Survey Ends - 1:55AM

Observation photos (11)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

    8 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC

    16.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    23.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    45.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    70.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    120.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 6", 2", 6" - Active

    145.2 ft. - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 6", 2", 6" - Active

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    239 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    244.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

Observations (22)

DistanceCodeObservation
2SAMSEVERE AGG
145.2TFIActive
255.3SRCLONG CIRCUM REBAR CORRODED
255.3SSSBLISTERING PEELING CONCRETE
0MGOConn. @ Mh, 9 O' Clock. OPEN
45.1SRCCIRCUM REBAR
255.3SAMSEVERE AGG
0AMH1:25AM
2SSSBLISTERING PEELING CONCRETE
244.3SRCLONG CIRCUM REBAR
0MWL
239SAMSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. Active
8SRCCIRCUM LONG REBAR
70.5SRCLONG CIRCUM REBAR
120.7SRCLONG CIRCUM REBAR
255.3MGOConn. @ Mh, 9 O' Clock. OPEN
23.1SRCCIRCUM REBAR
255.7AMH1:55AM
0MWM
255.3MGOConn. @ Mh, 3 O' Clock. Active
16.3SRCLONG CIRCUM REBAR SPORATIC

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2019-05-13T01:08:21-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false