Wastewater/Activity/PacpInspection/1.0May 10, 2019, 08:28 AM
  • 19 0120_19 0119_5102019_022057.mp4

Date
05/10/2019
W/O
0767442
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00722
PipeID
P15309
Time
1:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1206
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20190510MDM_EAST_ARTESIA_TRUNK_SECTS_1_2_3_5
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
19 0120
Downstream MH
19 0119
Dir. of Survey
Downstream
Length Surveyed
509.9 ft.
Total Length
509.9 ft.
Structural Index
3
Structural Quick
5242
Structural Rating
34
O&M Index
2
O&M Quick
3227
O&M Rating
20
Overall Index
3
Overall Quick
Overall Rating
54
Pipe schematic from manhole 19 0120 to 19 0119
MH: 19 0120MH: 19 0119downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area17.6 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - SLUDGE DEGRIE380.5 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - SLUDGE DEBRIE454.2 ft. ID - Infiltration Dripper, from 03 to 09 o'clock, within 8 inches of joint: YES460.2 ft. FC - Fracture Circumferential, from 06 to 07 o'clock, within 8 inches of joint: YES - SLIGHT-OFFSET460.2 ft. IW - Infiltration Weeper, from 03 to 04 o'clock, within 8 inches of joint: YES463 ft. B - Broken, from 05 to 12 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE OFFSET OUTWARD463 ft. B - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE-INSET463 ft. FC - Fracture Circumferential, from 06 to 05 o'clock, within 8 inches of joint: YES - SLIGHT466.3 ft. FC - Fracture Circumferential, from 12 to 05 o'clock, within 8 inches of joint: YES - SLIGHT472.4 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE474 ft. FC - Fracture Circumferential, from 06 to 05 o'clock, within 8 inches of joint: NO - SLIGHT474 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: NO - SLIGHT475.1 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: NO - SLIGHT & HAIRLINE475.1 ft. SSS - Surface Spalling, from 07 to 11 o'clock, within 8 inches of joint: NO - CHIPPING PIPE483.8 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES483.8 ft. IW - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES488.8 ft. FC - Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE490.3 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES - SLIGHT490.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES496.5 ft. DAE - Deposits Attached Encrustation, 2%of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES509.5 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO - INSIDE MH509.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active509.9 ft. AMH - Downstream Manhole, Survey Ends - 3:10AM

Observation photos (9)

  • Fracture Circumferential, from 06 to 07 o'clock, within 8 inches of joint: YES - SLIGHT-OFFSET

    460.2 ft. - Fracture Circumferential, from 06 to 07 o'clock, within 8 inches of joint: YES - SLIGHT-OFFSET

  • Broken, from 05 to 12 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE OFFSET OUTWARD

    463 ft. - Broken, from 05 to 12 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE OFFSET OUTWARD

  • Broken, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT  FRACTURE-INSET

    463 ft. - Broken, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT FRACTURE-INSET

  • Fracture Circumferential, from 06 to 05 o'clock, within 8 inches of joint: YES - SLIGHT

    463 ft. - Fracture Circumferential, from 06 to 05 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: NO - SLIGHT

    474 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: NO - SLIGHT

  • Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: NO - SLIGHT & HAIRLINE

    475.1 ft. - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: NO - SLIGHT & HAIRLINE

  • Surface Spalling, from 07 to 11 o'clock, within 8 inches of joint: NO - CHIPPING PIPE

    475.1 ft. - Surface Spalling, from 07 to 11 o'clock, within 8 inches of joint: NO - CHIPPING PIPE

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    483.8 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO - INSIDE MH

    509.5 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO - INSIDE MH

Observations (26)

DistanceCodeObservation
466.3FCSLIGHT
475.1FMSLIGHT & HAIRLINE
460.2FCSLIGHT-OFFSET
472.4FCHAIRLINE
380.5DSZSLUDGE DEBRIE
483.8DAE
463BSLIGHT FRACTURE OFFSET OUTWARD
509.9AMH3:10AM
490.3FCSLIGHT
483.8IW
463BSLIGHT FRACTURE-INSET
0AMH2:25AM
488.8FCHAIRLINE
496.5DAE
0MWM
474FCSLIGHT
490.3DAE
460.2IW
17.6DSZSLUDGE DEGRIE
0MWL
475.1SSSCHIPPING PIPE
509.5DAGSINSIDE MH
463FCSLIGHT
474FMSLIGHT
454.2ID
509.5MGOConn. @ Mh, 3 O' Clock. Active

Properties (6)

custom_field_three
BROKEN PIPE WITH SLIGHT FRACTURE
custom_field_two
2
customer
LACSD
datetime
2019-05-10T01:28:52-07:00
documentation
MARTIN,REVELES
is_lateral_inspection
false