Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 8, 2019, 08:03 PM
  • 18 0442_18 0441_582019_132439.mp4

Date
05/08/2019
W/O
0767446
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00675
PipeID
P14293
Time
1:03 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
7977
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTE FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Maintenance Related
Project
20190508DF_FLORENCE_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
18 0442
Downstream MH
18 0441
Dir. of Survey
Downstream
Length Surveyed
344.7 ft.
Total Length
344.7 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 18 0442 to 18 0441
MH: 18 0442MH: 18 0441downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:05 PM0.1 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0.1 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"50.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"74.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"102.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"125.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"143.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open168.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"192.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"220 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4", 4"244.3 ft. TBC - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"268.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"296.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"320.5 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"342.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish342.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish344.7 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active344.7 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)344.7 ft. AMH - Downstream Manhole, Survey Ends - 1:38 PM

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open

    143.8 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open

Observations (24)

DistanceCodeObservation
0AMH1:05 PM
220TBC
342.8SAP
50.2TFC
296.4TFC
344.7MGOConn. @ Mh, 9 O' Clock. Active
268.3TBC
2SSS
0.1MWM
344.7MGOGREASE THROUGHOUT THE REACH (5%)
192.6TFA
320.5TBC
344.7AMH1:38 PM
125.2TFC
26.4TFC
244.3TBC
143.8TFOpen
168.2TFC
342.8SSS
0.1MGOConn. @ Mh, 3 O' Clock. Active
102.3TFC
74.2TFC
2SAP
0.1MWL

Properties (6)

additional_info
POST CLEANING EVALUATION ONLY.
custom_field_two
3
customer
LACSD
datetime
2019-05-08T13:03:28-07:00
documentation
FRANKLIN, CASTILLO, BRAR
is_lateral_inspection
false