Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2019, 10:53 AM
  • 19 0094_19 0093_572019_040634.mp4

Date
05/07/2019
W/O
0767442
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00722
PipeID
P15286
Time
3:53 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1200
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20190507MDM_EAST_ARTESIA_TRUNK_SECTS_1_2_3_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0094
Downstream MH
19 0093
Dir. of Survey
Downstream
Length Surveyed
434.9 ft.
Total Length
434.9 ft.
Structural Index
4
Structural Quick
5A41
Structural Rating
84
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
88
Pipe schematic from manhole 19 0094 to 19 0093
MH: 19 0094MH: 19 0093downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE8 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR9.4 ft. SRV - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: NO - LONG REBAR9.5 ft. MGO - General Observation - 70% MAG COAT START12.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR12.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG19.9 ft. MGO - General Observation - 20% MAG COAT START20.8 ft. MWM - Water Mark, 40 %of cross sectional area20.8 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG31.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING CONCRETE31.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG31.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLSTERING PEELING CNCRETE40.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR49.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR55.7 ft. TF - Tap Factory Made, at 08 o'clock, -, within 8 inches of joint: YES, 6" - Open58 ft. TF - Tap Factory Made, at 08 o'clock, -, within 8 inches of joint: YES, 6" - Open58 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR58 ft. SAV - Surface Aggregate Visible, from 09 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG69 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR101.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG109.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR113.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6" - Capped125.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR163.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active172.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE189.6 ft. MWM - Water Mark, 60 %of cross sectional area213.6 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LOING REBAR239.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open242.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR268.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active277.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start - LONG REBAR279.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR283.7 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Finish - LONG REBAR283.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR287.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active291.2 ft. MGO - General Observation - 80 MAG COAT START299.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG331.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active340.8 ft. SRC - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR391.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE393.5 ft. MGO - General Observation - 60% MAG COAT START434.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE434.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG434.5 ft. MGO - General Observation - 60% MAG COAT FINISH434.9 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (25)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    8 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: NO - LONG REBAR

    9.4 ft. - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: NO - LONG REBAR

  • General Observation - 70% MAG COAT START

    9.5 ft. - General Observation - 70% MAG COAT START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    12.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 20% MAG COAT START

    19.9 ft. - General Observation - 20% MAG COAT START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING CONCRETE

    31.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING CONCRETE

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    40.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    49.1 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    58 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    69 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    101.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    109.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    172.3 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Water Mark, 60 %of cross sectional area

    189.6 ft. - Water Mark, 60 %of cross sectional area

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LOING REBAR

    213.6 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LOING REBAR

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    242.4 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start - LONG REBAR

    277.5 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start - LONG REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    279.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - 80 MAG COAT START

    291.2 ft. - General Observation - 80 MAG COAT START

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    299.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    340.8 ft. - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    391.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • General Observation - 60% MAG COAT START

    393.5 ft. - General Observation - 60% MAG COAT START

Observations (51)

DistanceCodeObservation
31.6SSSSWOLLEN BLISTERING CONCRETE
434.5SSSBLISTERING PEELING CONCRETE
287.6TFActive
19.9MGO20% MAG COAT START
163.7TFActive
20.8MWM
12.7SRCCIRCUM REBAR
40.5SRCCIRCUM REBAR
9.4SRVLONG REBAR
331.1TFActive
8SAMSEVERE AGG
69SRVCIRCUM REBAR
0MGOConn. @ Mh, 3 O' Clock. Active
213.6SRVLOING REBAR
0AMH4:10AM
101.9SAVSEVERE AGG
31.6SAVSEVERE AGG
239.3TFOpen
283.7SRVLONG REBAR
49.1SRVCIRCUM REBAR
393.5MGO60% MAG COAT START
340.8SRCCIRCUM REBAR
12.7SAVSEVERE AGG
55.7TFOpen
189.6MWM
109.5SRCCIRCUM REBAR
291.2MGO80 MAG COAT START
2SSSBLISTERING PEELING CONCRETE
277.5SRVLONG REBAR
434.5SAVSEVERE AGG
434.9AMH5:00AM
31.6SSSBLSTERING PEELING CNCRETE
58TFOpen
9.5MGO70% MAG COAT START
268.8TFActive
0MWM
58SRVCIRCUM REBAR
434.5MGO60% MAG COAT FINISH
279.6SRCCIRCUM REBAR
58SAVSEVERE AGG
20.8SAMSEVERE AGG
113.9TFCCapped
172.3SSSPEELING CONCRETE
0MGOConn. @ Mh, 9 O' Clock. Active
125.2SRCCIRCUM REBAR
283.7SRCCIRCUM REBAR
8SRCCIRCUM REBAR
0MWL
242.4SRCCIRCUM REBAR
391.1SSSPEELING CONCRETE
299.1SAVSEVERE AGG

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED-LONG REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2019-05-07T03:53:19-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection