Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2019, 07:45 AM
  • G 0086_G 16_572019_023325.mp4

Date
05/07/2019
W/O
0767444
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P02220
Time
12:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1198
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20190503MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0086
Downstream MH
G 16
Dir. of Survey
Downstream
Length Surveyed
6.9 ft.
Total Length
6.9 ft.
Structural Index
5
Structural Quick
5541
Structural Rating
29
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
29
Pipe schematic from manhole G 0086 to G 16
MH: G 0086MH: G 16downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:30AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active LARGE INCOMING0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR4.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED BROKEN5 ft. SRV - Surface Reinforcement Visible, at 07 o'clock, within 8 inches of joint: NO - REBAR6.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - LONG CIRCUM BROKEN REBAR6.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR ROOF OF STRUCTURE6.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped BULKHEAD6.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG6.9 ft. AMH - Downstream Manhole, Survey Ends - 2:40AM

Observation photos (6)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    2.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED BROKEN

    4.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR CORRODED BROKEN

  • Surface Reinforcement Visible, at 07 o'clock, within 8 inches of joint: NO - REBAR

    5 ft. - Surface Reinforcement Visible, at 07 o'clock, within 8 inches of joint: NO - REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR ROOF OF STRUCTURE

    6.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR ROOF OF STRUCTURE

Observations (14)

DistanceCodeObservation
0MWM
6.4SRCLONG CIRCUM BROKEN REBAR
0AMH2:30AM
6.4SRCBROKEN REBAR ROOF OF STRUCTURE
2SRCLONG & CIRCUM REBAR
4.5SRCLONG CIRCUM REBAR CORRODED BROKEN
5SRVREBAR
6.4MGOConn. @ Mh, 9 O' Clock. Capped BULKHEAD
2.5SRCBROKEN REBAR
6.4SAMSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. Active LARGE INCOMING
6.9AMH2:40AM
0MWL
2SAMSEVERE AGG

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED BROKEN
custom_field_two
1
customer
LACSD
datetime
2019-05-07T00:45:10-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection