Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2019, 07:41 AM
  • G 0113_G 0086_572019_015253.mp4

Date
05/07/2019
W/O
0767444
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P02174
Time
12:41 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1198
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20190503MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0113
Downstream MH
G 0086
Dir. of Survey
Downstream
Length Surveyed
318.9 ft.
Total Length
318.9 ft.
Structural Index
5
Structural Quick
5541
Structural Rating
29
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
5
Overall Quick
Overall Rating
37
Pipe schematic from manhole G 0113 to G 0086
MH: G 0113MH: G 0086downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:50AM0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR2 ft. MGO - General Observation - 90% TILES MISSING2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES8.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR66.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR96.5 ft. MWM - Water Mark, 50 %of cross sectional area96.5 ft. MWL - Water Level, 40 %of cross sectional area158 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR238.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR318.3 ft. MGO - General Observation - 80% MISSING TILES FINISH318.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active LARGE INCOMING318.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR CORRODED BROKEN MISSING318.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES318.9 ft. AMH - Downstream Manhole, Survey Ends - 2:20AM

Observation photos (7)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN  MISSING REBAR

    8.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    66.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Water Mark, 50 %of cross sectional area

    96.5 ft. - Water Mark, 50 %of cross sectional area

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR

    158 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    238.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

Observations (19)

DistanceCodeObservation
0MGOConn. @ Mh, 3 O' Clock. Active
2SRCBROKEN MISSING REBAR
318.3MGO80% MISSING TILES FINISH
2MGO90% TILES MISSING
66.1SRCBROKEN MISSING REBAR
96.5MWM
0MWL
318.3MGOConn. @ Mh, 3 O' Clock. Active LARGE INCOMING
238.5SRCBROKEN REBAR
318.3SRCLONG & CIRCUM REBAR CORRODED BROKEN MISSING
0AMH1:50AM
318.9AMH2:20AM
0MWM
8.9SRCBROKEN MISSING REBAR
2SAMSEVERE AGG AREAS OF MISSING TILES
0MGOConn. @ Mh, 9 O' Clock. Active
318.3SAMSEVERE AGG AREAS OF MISSING TILES
96.5MWL
158SRCMISSING REBAR

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED BROKEN MISSING
custom_field_two
1
customer
LACSD
datetime
2019-05-07T00:41:03-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false