Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2019, 07:41 AM
  • G 0117_G 0116_562019_014621.mp4

Date
05/06/2019
W/O
0767444
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P01444
Time
12:41 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1196
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Capital Improvement Program Assesment
Project
20190503MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0117
Downstream MH
G 0116
Dir. of Survey
Downstream
Length Surveyed
525.9 ft.
Total Length
525.9 ft.
Structural Index
5
Structural Quick
5541
Structural Rating
29
O&M Index
5
O&M Quick
5200
O&M Rating
10
Overall Index
5
Overall Quick
Overall Rating
39
Pipe schematic from manhole G 0117 to G 0116
MH: G 0117MH: G 0116downstream0 ft. MGO - General Observation - 50% MISSING TILES 9 :00 TO 3:00 START0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES2 ft. MGO - General Observation - 70% MAG COAT START12.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CO LONG & CIRCUM REBAR CORRODED MISSING17.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - MISSING REBAR17.6 ft. MGO - General Observation - 25% MISSING TILES START52.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING REBAR AREAS OF MISSING TILES88.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR174.8 ft. MGO - General Observation - 80% MISSING TILES START% MISSING TILES175.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR308.4 ft. MGO - General Observation - 100% MISSING TILES401.6 ft. MWM - Water Mark, 90 %of cross sectional area414.7 ft. MGO - General Observation - 80% MISSING TILES488.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR525 ft. MGO - General Observation - 70% MAG COAT FINISH525 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN525 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR CORRODED MISSING525 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG525 ft. MGO - General Observation - 80% MISSING TILES FINISH525 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active525.9 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM

Observation photos (12)

  • General Observation - 50% MISSING TILES 9 :00 TO 3:00 START

    0 ft. - General Observation - 50% MISSING TILES 9 :00 TO 3:00 START

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - 70% MAG COAT START

    2 ft. - General Observation - 70% MAG COAT START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CO LONG & CIRCUM REBAR CORRODED MISSING

    12.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CO LONG & CIRCUM REBAR CORRODED MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING REBAR AREAS OF MISSING TILES

    52.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING REBAR AREAS OF MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    88.3 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

  • General Observation - 80% MISSING TILES START% MISSING TILES

    174.8 ft. - General Observation - 80% MISSING TILES START% MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    175.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

  • General Observation - 100% MISSING TILES

    308.4 ft. - General Observation - 100% MISSING TILES

  • Water Mark, 90 %of cross sectional area

    401.6 ft. - Water Mark, 90 %of cross sectional area

  • General Observation - 80% MISSING TILES

    414.7 ft. - General Observation - 80% MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

    488.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR

Observations (24)

DistanceCodeObservation
488.1SRCCORRODED MISSING REBAR
52.3SRCCORRODED MISSING REBAR AREAS OF MISSING TILES
525MGO70% MAG COAT FINISH
414.7MGO80% MISSING TILES
525MGOConn. @ Mh, 3 O' Clock. OPEN
525SRCLONG & CIRCUM REBAR CORRODED MISSING
525SAMSEVERE AGG
2SAMSEVERE AGG AREAS OF MISSING TILES
0MGO50% MISSING TILES 9 :00 TO 3:00 START
0MWM
308.4MGO100% MISSING TILES
525.9AMH2:50AM
401.6MWM
2MGO70% MAG COAT START
175.6SRCCORRODED MISSING REBAR
88.3SRCCORRODED MISSING REBAR
0MWL
174.8MGO80% MISSING TILES START% MISSING TILES
525MGO80% MISSING TILES FINISH
12.3SRCCO LONG & CIRCUM REBAR CORRODED MISSING
525MGOConn. @ Mh, 9 O' Clock. Active
17.6SRCMISSING REBAR
0AMH1:55AM
17.6MGO25% MISSING TILES START

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2019-05-06T00:41:54-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false