Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2019, 08:55 AM
  • J 0396_J 0395_372019_012834.mp4

Date
03/07/2019
W/O
0756080
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P21088
Time
12:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1139
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
46
Purpose
Capital Improvement Program Assesment
Project
20190307MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0395
Downstream MH
J 0396
Dir. of Survey
Upstream
Length Surveyed
360.6 ft.
Total Length
360.6 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
55
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
55
Pipe schematic from manhole J 0395 to J 0396
MH: J 0395MH: J 0396upstream0 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM0.4 ft. MGO - General Observation - ZOOM 20'23.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL32.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H45.6 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish - H128.5 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - H128.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H154.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H156.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H156.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H157.1 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SL171.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H198.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL198.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL226.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H235.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H241.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H241.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish - H241.3 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL246 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start - H249.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL253.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H266 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H267.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - H281.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H286.9 ft. MGO - General Observation - WHITE COATING ON PIPE ABOVE WATER MARK290.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL290.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL295.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H309.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H311.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT321.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE352.6 ft. MGO - General Observation - 27" VCP360.6 ft. AMH - Downstream Manhole, Survey Begins - 1:35AM360.6 ft. MWL - Water Level, 10 %of cross sectional area360.6 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (5)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    50.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • General Observation - WHITE COATING ON PIPE ABOVE WATER MARK

    73.7 ft. - General Observation - WHITE COATING ON PIPE ABOVE WATER MARK

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H

    79.3 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    94.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - H

    232.1 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - H

Observations (36)

DistanceCodeObservation
360.6AMH2:30AM
119.3FCH
124.9FLH
189.4FCH
8MGO27" VCP
232.1FLH
161.8FCSL
114.6FLH
111.4FLSL
204.4FCH
64.9FLH
161.8FCSL
73.7MGOWHITE COATING ON PIPE ABOVE WATER MARK
204.4FLH
50.8FLH
206.5FLH
70.4FCSL
232.1FLH
38.9FCHAIRLINE
360.2MGOZOOM 20'
119.3FLH
70.4FLSL
327.7FLH
337.5FLSL
133.7FCH
119.3FCSL
93FLH
94.6FLH
49.4FCSLIGHT
0AMH1:35AM
315FLH
0MWL
0MWM
203.5FCSL
106.8FLH
79.3FLH

Properties (8)

additional_info
REVERSE INSPECTION
custom_field_three
HAIRLINE FRACTURES JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2019-03-07T00:55:26-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false
year_laid
19950221